KMB-IIT-BOM-06.01.23-04

The subject plant is located in district of and falls under NIC Category-13. This assessment was carried out by the IEAC Center, IIT Bombay, during the course of the year 2023.

General Info

Principal Product

TEXTILE

Plant Area (Sq.ft)

15,000

No. of Employees

500

Production Hours

8,600

Annual Production

Annual Sales

Assessment Summary

Total Energy Costs(per year)

₹2,36,65,526

Total Recommended Investment(one time)

₹7,90,000

Total Recommended Savings(per year)

₹23,45,829

Energy Costs Calculation
Grid Electricity

Annual Usage

52,66,258

Unit

kWh

Unit Cost

₹4.55

Annual Cost

₹2,36,65,526

Total Energy Costs(per year)

₹2,36,65,526

Observations & Recommendations
CR - Compressor
ObservationRecommendationUnit SavingsAnnual SavingsInvestmentROIStatus
High Unloading hours for certain compressorsInstall VFD for particular compressors50,005₹2,27,523₹3000002.5
Leakage cfm is high in many machinesArrest leakages in Loom machine periodically2,00,068₹9,10,309₹100002.5
Pressure setting in looms is high around 5.5 bar. Recommended for cotton is 4.8 to 5 bar and for polyester 5 to 5.2 bar.Adjust regulator so that 0.2-0.4 bar pressure can be decreased which will give minimum 3 cfm savings per machine.81,846₹3,72,399₹02.5
HF - Humidification Plant
ObservationRecommendationUnit SavingsAnnual SavingsInvestmentROIStatus
Supply cfm is less than Return cfmRecommended Return cfm should be 95 % of supply cfm. Install VFD in return fan and optimize the speed accordingly to achieve the required supply return ratio.1,68,484₹7,66,602₹4000006.3
Return ducts of Looms are choked. It should be cleanedIt should be optimized by including VFD in Supply and Return fans.15,164₹68,996₹8000013.9