EAR/22-23/KISEM-04
The subject plant is located in district of and falls under NIC Category-37003. This assessment was carried out by the IEAC Center, IIT Gandhinagar, during the course of the year 2022.
General Info
Principal Product
Common Effluent Treatment
Plant Area (Sq.ft)
20,000
No. of Employees
250
Production Hours
8,400
Annual Production
Annual Sales
₹5,00,00,000
Assessment Summary
Total Energy Costs(per year)
₹2,61,27,248
Total Recommended Investment(one time)
₹3,24,601
Total Recommended Savings(per year)
₹23,73,041
Energy Costs Calculation
Electricity
Annual Usage
33,94,218
Unit
kWh
Unit Cost
₹6.5
Annual Cost
₹2,11,21,516
Wind Power
Annual Usage
6,67,088
Unit
kWh
Unit Cost
₹7.5
Annual Cost
₹50,05,732
Total Energy Costs(per year)
₹2,61,27,248
Observations & Recommendations
MT - Motors
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Dissolved Oxygen (DO) level in aeration unit is greater than the standard decided by GPCB | DO sensor based system required for monitoring of DO in the aeration tank: 1) ON & OFF of Blowers & 2) VFD based system-ACT 1 & ACT-2 Blowers. (Switching OFF of one blower from ACT-1 & ACT-2 for 12 hrs/day). | 3,65,083.2 | ₹23,73,040.8 | ₹2,00,000 | 1 | |
Motors are running under load | Monitor that motors if during load time they are running at less load replace the motor with smaller one. | 0 | ₹0 | ₹0 | 0 | |
Leakage from blower bellow | Replace rubber bellow with metallic bellow | 0 | ₹0 | ₹50000 | 0 | |
Continuous air leakage from 1/2" line just near the blower outlet line | Due to trip issue of blower, they are continuously loosing the air for that use pressure relief valve or pressure pre-set so that this issue can be avoided | 0 | ₹0 | ₹0 | 0 |
CPF - Capacitor & Power Factor
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Some Capacitor of APFC Transformer 1 is derated | Need to check the rated voltage at capacitor name plate and try to fix the voltage issue and if kVAR actual is less than rated then need to change derated capacitor to improve PF for and decrease the load current | Load current will reduce | ₹0 | ₹23,473 | 0 | |
Some Capacitor of APFC Transformer 2 is derated | Need to check the rated voltage at capacitor name plate and try to fix the voltage issue and if kVAR actual is less than rated then need to change derated capacitor to improve PF for and decrease the load current | 0 | ₹0 | ₹51,128 | 0 |