EAR/23-24/KISEM/IITGN-02/REV-01

The subject plant is located in district of and falls under NIC Category-37003. This assessment was carried out by the IEAC Center, IIT Gandhinagar, during the course of the year 2023.

General Info

Principal Product

Final Effluent Treatment Plant

Plant Area (Sq.ft)

1,00,000

No. of Employees

200

Production Hours

7,200

Annual Production

Annual Sales

₹1,00,00,00,000

Assessment Summary

Total Energy Costs(per year)

₹15,77,08,712

Total Recommended Investment(one time)

₹47,00,000

Total Recommended Savings(per year)

₹2,43,62,952

Energy Costs Calculation
Electricity

Annual Usage

1,77,20,080

Unit

kWh

Unit Cost

₹8.9

Annual Cost

₹15,77,08,712

Total Energy Costs(per year)

₹15,77,08,712

Observations & Recommendations
DM - Demand Management
ObservationRecommendationUnit SavingsAnnual SavingsInvestmentROIStatus
High Contract Demand (average demand last year is 2400 kVA)Reduced the contract demand by 2700 kVA₹13,53,000₹3,00,0003
Leading Power Factor in the plantSwitch off some capacitor will also help to reduce the Contract Demand (100 kVA)₹3,00,000
BL - Blower
ObservationRecommendationUnit SavingsAnnual SavingsInvestmentROIStatus
Aeration (A1 & A2) area motor are running on 50 Hz with VFDReduce the frequency of aeration motor by 2 Hz227760₹18,22,080₹24,00,0001
Aeration (B1 & B2) area motor are running on 50 Hz with VFDReduce the frequency of aeration motor by 2 Hz245280₹19,62,240
Aeration (C1 & C2) area motor are running on 50 Hz with VFD Reduce the frequency of aeration motor by 2 Hz341640₹27,33,120
VFD of aeration tank (A3 & A4) running in manual mode although they have sensorsTake feedback back from dissolved oxygen sensor and give it to VFD for controlling the speed of motor353520₹28,28,160
VFD of aeration tank (B3 & B4) running in manual mode although they have sensorsTake feedback back from dissolved oxygen sensor and give it to VFD for controlling the speed of motor1005120₹80,40,960
VFD of aeration tank (C3) running in manual mode although they have sensorsTake feedback back from dissolved oxygen sensor and give it to VFD for controlling the speed of motor258480₹20,67,840
Some Aeration Blowers are not capable to deliver the flowReplace with highly efficient blowers (details are provided in the report)
PP - Pumps
ObservationRecommendationUnit SavingsAnnual SavingsInvestmentROIStatus
Efficiency of filter press feed pump is low (nearly 50%)Replace with highly efficient pumps (70%)69,360₹5,54,880₹6,00,00013
Feed pump motor is overrated (45kW)When low efficient pump is replaced by highly efficient pump helps to reduce the motor rated power to 30 kW37,584₹3,00,672₹6,00,00024
Bypassing the flow due to back pressure of filter pressUse VFD with Pressure transmitter in line so that VFD control the speed of motor as pressure increase3,00,000₹24,00,000₹8,00,0004