EAR/23-24/KISEM-04
The subject plant is located in district of and falls under NIC Category-52101. This assessment was carried out by the IEAC Center, IIT Gandhinagar, during the course of the year 2023.
General Info
Principal Product
Cold Storage
Plant Area (Sq.ft)
1,00,000
No. of Employees
100
Production Hours
8,760
Annual Production
Annual Sales
₹3,00,00,000
Assessment Summary
Total Energy Costs(per year)
₹24,94,521
Total Recommended Investment(one time)
₹2,30,000
Total Recommended Savings(per year)
₹7,68,615
Energy Costs Calculation
Electricity
Annual Usage
3,28,609
Unit
kWh
Unit Cost
₹7.6
Annual Cost
₹24,94,521
Solar Energy
Annual Usage
1,31,609
Unit
kWh
Unit Cost
₹
Annual Cost
₹
Total Energy Costs(per year)
₹24,94,521
Observations & Recommendations
TR - Transformer
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Current harmonics (5th and 7th) present in the system is 326% and 383% at an average of. i.e,48.9% and 54.7% respectively while standard is 8% | Install 7% detune capacitor | 78,317 | ₹5,87,374.2 | ₹1,00,000 | 2 | |
Current harmonics (5th and 7th) present in the system is 26.1% and 23.6 at an average of. i.e ,21% and 22% respectively while standard is 8% | Install 7% detune capacitor | 12519 | ₹93,895 | ₹70,000 | 9 |
HVC - Heating Ventilation & Cooling
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Supply and exhaust duct required for CO2 exhaust or ventilation system (4 units) not insulated | Proper Insulation required | 6,655 | ₹49,912.50 | ₹30,000 | 6 | |
Supply and exhaust duct required for CO2 exhaust or ventilation system (3 units) not insulated | Proper Insulation required | 4991 | ₹37,433 | ₹30,000 | 10 |