KMB-IIT-MAD-13.09.22-09
The subject plant is located in Nagondapalli district of Tamil Nadu and falls under NIC Category-26521. This assessment was carried out by the IEAC Center, IIT Madras, during the course of the year 2022.
General Info
Principal Product
Watch case for Titan watches
Plant Area (Sq.ft)
30,000
No. of Employees
50
Production Hours
7,200
Annual Production
50,00,000
Annual Sales
₹50,00,000
Assessment Summary
Total Energy Costs(per year)
₹34,68,428
Total Recommended Investment(one time)
₹3,23,000
Total Recommended Savings(per year)
₹5,49,640
Energy Costs Calculation
Electricity
Annual Usage
4,88,832
Unit
kWh
Unit Cost
₹7.5
Annual Cost
₹34,68,428
Total Energy Costs(per year)
₹34,68,428
Observations & Recommendations
CPF - Capacitor & Power Factor
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Poor Power Factor | Replace the de-rated capacitors with new capacitors | 1,500 | ₹11,250 | ₹45,000 | 48.0 | |
Poor Power Factor | Replace the de-rated capacitors with new capacitors | 500 | ₹3,750 | ₹5,000 | 16.0 |
CR - Compressor
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Medium Air Leakage | Eliminate leaks in inert gas and compressed air lines/ valves | 23,721 | ₹1,77,908 | ₹50,000 | 3.4 | |
Capacity Underutilization | The compressor should be effectively operated in a manner that it should have minimum number of unloading cycles | 9,063 | ₹67,973 | ₹75,000 | 13.2 | |
Capacity Underutilization | The compressor should be effectively operated in a manner that it should have minimum number of unloading cycles | 4,260 | ₹31,950 | ₹0 | 0.0 |
MT - Motors
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Excess Capacity for Process | Remove excess capacity utilities with respect to the process requirement | 5,979 | ₹44,843 | ₹0 | 0.0 |
HVC - Heating Ventilation & Cooling
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Poor Maintenance of Heater Transformer | Periodically check for heater transformer performance and replace if necessary | 16,215 | ₹1,21,613 | ₹50,000 | 4.9 | |
Poor Maintenance of Heater Transformer | Periodically check for heater transformer performance and replace if necessary | 8,550 | ₹64,125 | ₹50,000 | 9.4 |
FN - Fans
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Old Type Fans | Use BLDC fan with equivalent velocity | 958 | ₹7,185 | ₹28,000 | 46.8 |
LT - Lighting
Observation | Recommendation | Unit Savings | Annual Savings | Investment | ROI | Status |
---|---|---|---|---|---|---|
Incandescent Type Tube Lights | Substitute Higher-Efficiency Lamps for Incandescent Lamps | 2,539 | ₹19,043 | ₹20,000 | 12.6 |